Proper Wire Sizing
Below is a chart that shows the proper wire sizing for the current flowing in your vessel.
Ensure you verify requirements and check with properly authorized electricians for installations.

What size wire should be used?
1. Calculate the maximum sustained amperage of the circuit. Measure the length of the circuit
from the power source to the load and back.
2. Decide whether the circuit runs in an engine space or non-engine space. Engine spaces are
assumed to be at 50 degrees C, non-engine spaces are assumed to be at 30 degrees C.
3. Multiply the maximum current times the length of the circuit to calculate Famps (Feet x amps).
4. Base the wire on either the 3% or 10% voltage drop. In general, items which affect the safe
operation of the boat and its passengers (running lights, bilge blowers, electronics and
distribution panel supply circuits) use 3%; all other loads use 10% (cabin lights, pumps).
5. Starting in the column which has the right voltage and voltage drop shown at the top, run down
the list of numbers until arriving at a value which is greater than the calculated Famps. Move
left to the Ampacity column to verify that the total amperage of the circuit does not exceed the
maximum allowable amperage of the wire size for that row. If it does, move down until the wire
ampacity exceeds the circuit amperage. Finally, move left to the wire size column to select the
wire size.
Examples
1. A 12 volt system at 10% drop with a 40' circuit x 45 amps = 1800 Famps. A wire size of 8 is
required.
2. A 24 volt system at 3% drop with a 10' circuit x 100 amps = 1000 Famps. A wire size of 6 is
required.
Note:
We discovered that depending on distance, a wire size of 8, 6, or larger awg may be required as a minimum for
some refrigeration systems. Proper wire sizing prevents system shutdown on start up due to too high a resistance
being created in an undersized wire. One would normally think that 10 awg wire (60 amps usable, outside of
engine spaces) would be sufficient for a 10-15 amp loaded circuit. However, the 348 famps limit will easily
be exceeded with a moderate (over 11 feet) circuit run. Remember to use the round trip, not one way, distance
when calculating Famps.